9000HP 13800V Hyundai N5000 Medium Voltage VFD, Inverter, AC Drive N5000-6670U6
Brand: HYUNDAI
Model: N5000-6670U6
Condition: New
Technical Specifications
Phase Rating | 3 Phase Input - 3 Phase Output |
---|---|
Series | N5000 |
Phase | Three Phase |
Rated Amps | 350 A |
Enclosure Rating | IP 41 |
Brand | HYUNDAI |
Horsepower Rating | 9000 HP |
Rated Voltage | 13800 V |
Product Condition | New |
Output Voltage | 13800 V |
Output Amperage Rating | 350 A |
HP Rating @ 120% OL | 9000 HP |
Amp Rating @ 120% OL | 350 A |
Model | N5000-6670U6 |
Product Information
HYUNDAI N5000 Series
High Performance and Efficiency
- Power Factor: over 0.95
- No requirements for power factor correction capacitor
- System Efficiency: over 96%
- System efficiency is improved by connecting the power and motor without input-output filter and output transformer
Clean Power Input
- A clean input wave is achieved via a secondary phase-shifted transformer
- Without a filter, N5000 meets the stringent harmonic requirements of IEEE-519 (1992)
- Protects the other equipment from harmonic disturbance
Supplies of Clean Power for Motors
- Output waveforms, without a filter, are close to sine waves due to multiple PWM control
- No cable length & motor type restrictions
- Existing motor can be used without modifications
- Reduced noise and vibration of motors
- 3.3kV - 13 level/6.6kV - 25 level output
Small footprint and economical maintenance
- Small footprint and reduced installation costs due to no requirements for ancillary equipment such as input & output filter and the integral structure incorporating the input transformer and inverter panel
- Thanks to the modular single-phase inverter of draw-out type, easy maintenance and time saving are achieved.
Outstanding operation features by the improved sensorless vector control
- Energy saving V/F control for the fluid load (Fan, Pump)
- Inherent speed sensorless vector control of N5000
- High starting torque operation
- Control of current, speed and vibration of motor at the low speed range of light duty
- Quick torque responsiveness and improved speed precision
- Strong control regardless of motor specifications
Functions for trip-free operation (Option)
Improved Cell Bypass
- In case of cell failure during operation, the faulty cell will be bypassed and the neutral point will be shifted (balance is restored through angle adjustment). 92% of the rated voltage can be output after the failure of one cell.
Redundant Inverter Controller
- If the master controller is out of service during operation, output is generated due to automatic switching to the slave controller
Redundant Fiber-Optic Cable for CAN Communication
- If there are problems with the optic cable during operation, an automatic switching to the standby reserve optical communication H/W is made
Redundant Control Power
- The redundant control power module is equipped with AC 440V and DC 120V and monitors the control power. In case of the failure of a control power module, an automatic switching to the reserve module is made
Certification (Korea Electro-Technology Research Institute)
Performance Test: Harmonics, Power Factor & Control
Environmental Tests of Cell Inverter and Control Parts: Constant Temperature, Vibration, EMI/EMC
Display
Inverter Operation Status Display
- Operation frequency, input-output voltage, output current
- Input-output of external signals
- Warning status
Inverter Fault Display
- Fault type
- Time of Fault
- Operating frequency at time of fault
- Voltage and current at time of fault
Optional User Friendly PC-based Console (Option)
- Remote operation and monitoring via laptop or desktop
- Easy parameter setting and monitoring
- Multiple communication interfaces (RS-232, RS-485, MODBUS)
- Custom-made MMI display and upgrade support
   Ask a question